4706
Breaker 1 close
0 to 65535
---
1
F300
0
4707
Breaker 1 phase A / three-pole closed
0 to 65535
---
1
F300
0
4708
Breaker 1 phase B closed
0 to 65535
---
1
F300
0
4709
Breaker 1 phase C closed
0 to 65535
---
1
F300
0
470A
Breaker 1 external alarm
0 to 65535
---
1
F300
0
470B
Breaker 1 alarm delay
0 to 1000000
s
0.001
F003
0
470D
Breaker 1 pushbutton control
0 to 1
---
1
F102
0 (Disabled)
470E
Breaker 1 manual close recall time
0 to 1000000
s
0.001
F003
0
4710
Breaker 1 out of service
0 to 65535
---
1
F300
0
4711
Breaker 1 block open
0 to 65535
---
1
F300
0
4712
Breaker 1 block close
0 to 65535
---
1
F300
0
4713
Breaker 1 phase A / three-pole opened
0 to 65535
---
1
F300
0
4714
Breaker 1 phase B opened
0 to 65535
---
1
F300
0
4715
Breaker 1 phase C opened
0 to 65535
---
1
F300
0
4716
Breaker 1 operate time
0 to 2
s
0.001
F001
70
4717
Breaker 1 events
0 to 1
---
1
F102
0 (Disabled)
4718
Reserved
---
---
---
---
---
4719
...Repeated for breaker 2
4732
...Repeated for breaker 3
474B
...Repeated for breaker 4
Synchrocheck (Read/Write Setting) (2 modules)
47A0
Synchrocheck 1 Function
0 to 1
---
1
F102
0 (Disabled)
47A1
Synchrocheck 1 V1 Source
0 to 5
---
1
F167
0 (SRC 1)
47A2
Synchrocheck 1 V2 Source
0 to 5
---
1
F167
1 (SRC 2)
47A3
Synchrocheck 1 Maximum Voltage Difference
0 to 400000
V
1
F060
10000
47A5
Synchrocheck 1 Maximum Angle Difference
0 to 100
degrees
1
F001
30
47A6
Synchrocheck 1 Maximum Frequency Difference
0 to 2
Hz
0.01
F001
100
47A7
Synchrocheck 1 Dead Source Select
0 to 5
---
1
F176
1 (LV1 and DV2)
47A8
Synchrocheck 1 Dead V1 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
47A9
Synchrocheck 1 Dead V2 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
47AA
Synchrocheck 1 Live V1 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
47AB
Synchrocheck 1 Live V2 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
47AC
Synchrocheck 1 Target
0 to 2
---
1
F109
0 (Self-reset)
47AD
Synchrocheck 1 Events
0 to 1
---
1
F102
0 (Disabled)
47AE
Synchrocheck 1 Block
0 to 65535
---
1
F300
0
47AF
Synchrocheck 1 Frequency Hysteresis
0 to 0.1
Hz
0.01
F001
6
47B0
...Repeated for Synchrocheck 2
Flexcurves A and B (Read/Write Settings)
4800
FlexCurve A (120 items)
0 to 65535
ms
1
F011
0
48F0
FlexCurve B (120 items)
0 to 65535
ms
1
F011
0
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
0 to 65535
---
1
F001
0
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
---
---
---
F202
“ “
4C0A
User-Definable Display 1 Bottom Line Text
---
---
---
F202
““
4C14
Modbus Addresses of Display 1 Items (5 items)
0 to 65535
---
1
F001
0
4C19
Reserved (7 items)
---
---
---
F001
0
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
Table B–9: MODBUS MEMORY MAP (Sheet 15 of 55)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...