5-30
L60 Line Phase Comparison System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850 PROTOCOL
ÖØ
XCBR CONFIGURATION
The
CLEAR XCBR1 OpCnt
setting represents the breaker operating counter. As breakers operate by opening and closing, the
XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result
in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1.
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850 PROTOCOL
ÖØ
XSWI CONFIGURATION
The
CLEAR XSWI1 OpCnt
setting represents the disconnect switch operating counter. As disconnect switches operate by
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net-
work routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN
functionality.
XCBR
CONFIGURATION
XCBR1 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
XCBR2 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
↓
MESSAGE
XCBR6 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
CLEAR XCBR1 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XCBR2 OpCnt:
No
Range: No, Yes
↓
MESSAGE
CLEAR XCBR6 OpCnt:
No
Range: No, Yes
XSWI
CONFIGURATION
XSWI1 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
XSWI2 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
↓
MESSAGE
XSWI24 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
CLEAR XSWI1 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XSWI2 OpCnt:
No
Range: No, Yes
↓
MESSAGE
CLEAR XSWI24 OpCnt:
No
Range: No, Yes
NOTE
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...