B-22
L60 Line Phase Comparison System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
42DE
...Repeated for User-Programmable LED 48
Installation (Read/Write Setting)
43E0
Relay Programmed State
0 to 1
---
1
F133
0 (Not Programmed)
43E1
Relay Name
---
---
---
F202
“Relay-1”
User Programmable Self Tests (Read/Write Setting)
4441
User Programmable Detect Ring Break Function
0 to 1
---
1
F102
1 (Enabled)
4442
User Programmable Direct Device Off Function
0 to 1
---
1
F102
1 (Enabled)
4443
User Programmable Remote Device Off Function
0 to 1
---
1
F102
1 (Enabled)
4444
User Programmable Primary Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
4445
User Programmable Secondary Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
4446
User Programmable Battery Fail Function
0 to 1
---
1
F102
1 (Enabled)
4447
User Programmable SNTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
4448
User Programmable IRIG-B Fail Function
0 to 1
---
1
F102
1 (Enabled)
4449
User Programmable Ethernet Switch Fail Function
0 to 1
---
1
F102
0 (Disabled)
CT Settings (Read/Write Setting) (6 modules)
4480
Phase CT 1 Primary
1 to 65000
A
1
F001
1
4481
Phase CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4482
Ground CT 1 Primary
1 to 65000
A
1
F001
1
4483
Ground CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4484
...Repeated for CT Bank 2
4488
...Repeated for CT Bank 3
448C
...Repeated for CT Bank 4
4490
...Repeated for CT Bank 5
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (3 modules)
4500
Phase VT 1 Connection
0 to 1
---
1
F100
0 (Wye)
4501
Phase VT 1 Secondary
50 to 240
V
0.1
F001
664
4502
Phase VT 1 Ratio
1 to 24000
:1
1
F060
1
4504
Auxiliary VT 1 Connection
0 to 6
---
1
F166
1 (Vag)
4505
Auxiliary VT 1 Secondary
50 to 240
V
0.1
F001
664
4506
Auxiliary VT 1 Ratio
1 to 24000
:1
1
F060
1
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
Source Settings (Read/Write Setting) (6 modules)
4580
Source 1 Name
---
---
---
F206
“SRC 1"
4583
Source 1 Phase CT
0 to 63
---
1
F400
0
4584
Source 1 Ground CT
0 to 63
---
1
F400
0
4585
Source 1 Phase VT
0 to 63
---
1
F400
0
4586
Source 1 Auxiliary VT
0 to 63
---
1
F400
0
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
25 to 60
Hz
1
F001
60
4601
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
4602
Frequency And Phase Reference
0 to 5
---
1
F167
0 (SRC 1)
4603
Frequency Tracking Function
0 to 1
---
1
F102
1 (Enabled)
Breaker control (read/write settings)
4700
Breaker 1 function
0 to 1
---
1
F102
0 (Disabled)
4701
Breaker 1 name
---
---
---
F206
“Bkr 1"
4704
Breaker 1 mode
0 to 1
---
1
F157
0 (3-Pole)
4705
Breaker 1 open
0 to 65535
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 14 of 55)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...