CPR 126 

CURRENT PROTECTION RELAY

TECHNICAL SPECIFICATION

MECHANICAL INSTALLATION

TERMINAL CONNECTION

FEATURES:

INPUT SPECIFICATION:

DISPLAY AND KEY:

OUTPUT SPECIFICATION:

AUXILIARY SUPPLY:

GENERAL SPECIFICATION:

Primary CT value

True RMS Measurement

Protection available

Over Load

Auto/Manual /ZVR (Zero Value Reset) reset option

Under Load

3 digit bright LED display

Current Asymmetry

Three phase current display with LED indication

Single phase prevention (i.e it can trip relay in case of 
any phase current is become zero)

Auto save out feature

Time parameter : Power on delay
                              Trip delay
                              Initial time delay
                              Recovery time (Auto reset)

Secondary current AC

Resolution

5 to 999 Selectable

0.5 to 5 Amp AC

0.01A, 0.1A,  1A

Display

Relay

Supply voltage

Dimension (mm) 

Keys

Relay Type

Power consumption
(VA RATING)

Rating

Trip Setting

Time parameter

3 digit, 1line, 7 seg, 0.4” RED LED

1 nos.

75 (H) x 45 (W) x 110 (D) mm

SET, INC, DEC/ RST

1  C/O (NO-C-NC)

3 VA @ 230V AC MAX

10A, 230V AC/28 V DC

Under current : 0.00 to 100% of
primary C.T value

Trip delay time : 0 to 999 sec
Power on time : 0 to 99 sec
Initial time delay : 0 to 99 sec 

Over current : 0.00 - 125% of
primary C.T value

ENVIRONMENT CONDITION:

Relative Humidity

 Operating Temp.

0°C to 55°C

UP to 95% RH 
(non-condensing)

100 to 270V AC, 50-60Hz

Recovery time : 0 to 99 sec

110

Front View(mm)

A

SET

NO

L

N

C NC

CPR 126

A1

R

A2 A3

4 0 0

75

Side View(mm)

75

45

NO

L

N

C NC

CPR 126

A1

R

A2 A3

A

SET

L1

L2

L3

N

TO

LOAD

Class 1.0 (Standard)

ACCURACY

Summary of Contents for CPR 126

Page 1: ...ery time Auto reset Secondary current AC Resolution 5 to 999 Selectable 0 5 to 5 Amp AC 0 01A 0 1A 1A Display Relay Supply voltage Dimension mm Keys Relay Type Power consumption VA RATING Rating Trip Setting Time parameter 3 digit 1line 7 seg 0 4 RED LED 1 nos 75 H x 45 W x 110 D mm SET INC DEC RST 1 C O NO C NC 3 VA 230V AC MAX 10A 230V AC 28 V DC Under current 0 00 to 100 of primary C T value Tr...

Page 2: ... clamp so the instrument fits on the DIN rail 2 Ensure proper fitting of the instrument by pulling it outwards 3 To remove the instrument raise the clamp to release it from the DIN rail 4 The equipment in its installed state must not come in close proximity to any heating source caustic vapors oil steam or other unwanted process byproducts 5 Do not connect anything to unused terminals INSTALLATION...

Page 3: ... Press key for 5 sec SET Press key for 5 sec NOTE If Auxiliary supply cut out without fault Reset Then fault will be display at next power on If Reset Mode Selected As ZVR Zero Value Reset then the Relay will be reset after Selected Reset time once the healthy condition achieved OR Zero Value reached SET To Reset fault press key O C O C A2 A3 R A1 3 4 5 A2 A3 R A1 Scroll Over current in R Phase Ov...

Page 4: ...covery time Press key Press key Press key SET SET SET If manual reset mode select 0 to 99 sec If Auto ZVR reset mode select Under Current Under Current Enable RLY fault OFF Power on time 5 sec Initial time delay 5 sec Trip delay time 5 sec Current U C Set point OFF TRP Time ON 5 10 15 20 Power On ITD TRP Delay OFF R Y B Reset mode Manual Page 2 Asymmetry Current Over Current Current SPP Enable Asy...