Critical Power
Modifications reserved
Page 79/146
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
User Manual
TLE Series 600 & 800 CE S1
LOAD SCREEN
Voltage L1 / L2 / L3
Output voltage PHASE/NEUTRAL for each
phase.
Current L1 / L2 / L3
The output current as RMS values for
each phase.
Percent load L1 / L2 / L3
The output Load as percentage for each
phase.
Active power
Load active power (kW) for each phase.
Apparent power
Load apparent power (kVA) for each phase.
Power factor
Load power factor: + inductive load / - capacitive load
Status
Source of the power supplied to the Load.
Apparent power
Total apparent Load power (kVA).
Active Power
Total effective Load power (kW).
Overload counter
Total number of detected output overloads.
Inverter operating time
Total operating time for the Inverter (in hours).
UPS operation time
Total operating time for the UPS (in hours).
eBoost operation time
Total operating time for the UPS in
eBoost™ Operation Mode
(in hours).
This counter is displayed only when
eBoost™ Operation Mode
is available
(option).
IEMi operation time
Total operating time for the UPS in
IEMi Operation Mode
(in hours).
This counter is displayed only when
IEMi Operation Mode
is available (option).
BOOSTER SCREEN
Battery voltage
The battery voltage.
Battery current
The battery current (negative values
correspond to the discharge of the
battery).
Voltage DC-link 1
DC-link 1 voltage.
Voltage DC-link 2
DC-link 2 voltage.
Status
Booster status (Off / Booster / Charger).
Temperature
Temperature of the 4
th
leg’s bridge.
Temperature a / b / c / d
a-
Booster temperature (lower left module).
b-
Booster temperature (upper left module).
c-
Booster temperature (lower right module).
d-
Booster temperature (upper right module
–
only for 800 kVA).