Critical Power
Modifications reserved
Page 117/146
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
User Manual
TLE Series 600 & 800 CE S1
8.2.3
Restore to normal operation after “System shutdown”
with Load not supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before
proceeding, as this procedure will result in the connection of power to the load
circuit(s).
NOTE !
Before performing this operation, make sure that the UPS is in the following status:
“Q1
- UPS Output
switch”
MUST BE CLOSED.
“External Battery Protections”
MUST BE DISCONNECTED.
View of the
Synoptic Diagram
after performed the
command “
System shutdown”,
with LOAD NOT
SUPPLIED.
1. Restore the command
“
System shutdown”
.
Restore the command
“
System shutdown
” through
the screen:
Commands 1 / System shutdown /
RESET
NOTE !
Ensure the
LED 1 (Rectifier)
is lit before carrying out this procedure.
It indicates that the DC-Link has reached 800Vdc (see screen
MEASURES / Rectifier)
!
2. Connect the Battery to the UPS by closing the
“
External
Battery Protections”.
NOTE !
Before performing the next procedure make sure that the
LED 3 (Booster/Battery charger)
is
lit.
Continue
►