TLE Series 600 & 800 CE S1
9.2
CUSTOMER INTERFACE BOARD
Fig. 9.2-1 Customer Interface Board
J1 connector
–
RJ45 8P8C (see Section 9.2.1)
Pin 5
: TX (out)
Pin 6
: RX (in)
Pin 4
: GND
X1 terminal block
–
Output signals on voltage free contacts (see Section 9.2.2)
X1 / 1, 2, 3
NO, C, NC
MAINS FAILURE
(def. Parameter RL=1)
X1 / 4, 5, 6
NO, C, NC
LOAD ON INVERTER
(def. Parameter RL=3)
X1 / 7, 8, 9
NO, C, NC
STOP OPERATION
(def. Parameter RL=5)
X1 / 12, 13, 14
NO, C, NC
LOAD ON MAINS
(def. Parameter RL=2)
X1 / 15, 16, 17
NO, C, NC
GENERAL ALARM
(def. Parameter RL=4)
X1 / 18, 19, 20
NO, C, NC
BUZZER (acoustic alarm) (def. Parameter RL=6)
The programmable signals on
X1
will be disabled with
Q1
open, with the
exception of the signals for
“16
- MANUAL BYPASS ON
”
and
“26 –
EMERGENCY
OFF (EPO)
”
.
X1 terminal block
–
Input contacts (see Section 9.2.3)
X1 / 10, 21
NO
Programmable
X1 / 11, 22
NO
Programmable / GENERATOR ON
X2 terminal block
–
EPO -Emergency Power Off connection (see Section 9.2.4)
X2 / 1, 2
NC
EPO (Emergency Power Off)
Note: to enable this function, remove the
Jumper JP2
on
“
P4
–
Customer
Interface
”
board
(see
Section 9.2.4).
NO
= Normally Open
C
= Common
NC
= Normally Closed
Output signals on voltage-free contacts
Programmable functions on input contacts
On terminals
X1
,
6
of the following
27 signals
can be selected
from the display, entering with the appropriate password.
Some UPS functions can be activated with
parameters when an external Normally
Open (NO) contact is closed on:
X1/10, 21
or
X1/11, 22
Selectable
functions
by
changing
parameters
(password required) are:
0 - NO FUNCTION
1 - INVERTER ON
2 - INVERTER OFF
3
–
PRINT ALL
4 - STATUS RELAY
5 - GENERATOR ON
6 - EXTERNAL BYPASS
7 - BATTERY FUSES OR EXTERNAL K3
(See Alarm 4104 - Battery Fuses)
8 - eBoost/IEMi CONTROL
Voltage free contacts:
Max. 24Vac / 1A or 60Vdc / 0,5A
IEC-UL-CSA 60950-1 (SELV circuit)
Min. Signal Level: 5Vdc / 5mA
0- NO SIGNAL
1- BUZZER
2- GENERAL ALARM
3- LOAD ON MAINS
4- STOP OPERATION
5- LOAD ON INVERTER
6- MAINS FAILURE
7- DC OVERVOLTAGE
8- LOW BATTERY
9- OVERLOAD
10- OVERTEMPERATURE
11- INVERTER-BYPASS NOT SYNCHR.
12- BYPASS LOCKED
13- BYPASS MAINS FAILURE
14- RECTIFIER MAINS FAILURE
15- BATTERY DISCHARGE
16- MANUAL BYPASS ON
17- RECTIFIER ON
18- INVERTER ON
19- BOOST CHARGE
20- BATTERY EARTH FAULT
21- BATTERY FAULT
22- RELAY INPUT 1
23- RELAY INPUT 2
24- RELAY OUTPUT ON
25- RELAY OUTPUT OFF
26- EMERGENCY OFF (EPO)
27- eBoost/IEMi MODE
1
2
8
19
21
22
20
10
11
9
17
18
16
15
7
6
5
4
12
14
13
3
2
1
X1
X2
J1
SG
SE
_400-
500_
S1_C
ust
ome
r i
nt
erf
ace_01