Critical Power
Modifications reserved
Page 127/146
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
User Manual
TLE Series 600 & 800 CE S1
3.
Perform the command “Module shutdown”
on the
Unit to separate only when the symbol Q1 in the
Synoptic Diagram is shown open.
Perform the command
“
Module shutdown
” through
the
screen:
Commands 1 / Module shutdown /
SHUTDOWN
.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
4. Disconnect the Battery on the Unit to separate by opening the
“External Battery Protections”
.
Press
“MUTE”
key to reset
Acoustical Alarm
.
LED ALARM
remains lit.
NOTE !
Before performing the next procedure wait 5 minutes for
DC-Link Capacitors
discharge.
Use the
MEASURES/Rectifier
screen to ensure that the
DC-link1 and DC-link 2
voltage
has reached 10Vdc.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
5. Disconnect the Mains supply on the Unit to separate
.
LCD display is Off
Synoptic diagram of the unit to separate
Synoptic diagram of other units
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
NOTE !
For any further intervention contact nearest
Service Centre
.