Critical Power
Modifications reserved
Page 97/146
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
User Manual
TLE Series 600 & 800 CE S1
COMMANDS 1 SCREEN
Allows the user to execute UPS
operation commands.
Rectifier
Rectifier ON
Rectifier switching ON command.
Rectifier RESET
Rectifier restore command.
Reserved for the
Service Centre
.
Led Rectifier status
Indicates the Rectifier’s status
: ON = lit
OFF = turned Off
Inverter
Inverter ON
Inverter switching ON command.
NOTE !
When
eBoost™ Operation Mode
or
IEMi Operation Mode
is enabled, control of
Inverter status and selection of the feed path is done autonomously by the
UPS control logic.
Therefore,
Inverter ON / Inverter OFF
commands are disabled when
eBoost™
Operation Mode
or
IEMi Operation Mode
is enabled.
Inverter OFF
Inverter switching OFF command.
This command is also used as
EPO (Emergency Power Off)
reset after the contact closing.
NOTE !
Inverter OFF
command is disabled when
eBoost™ Operation Mode
or
IEMi
Operation Mode
is enabled.
Led inverter status
It indicates the Inverter status:
ON / OFF / Pre-charge / Pre-charge completed / Soft-start