User Manual
TLE Series 600 & 800 CE S1
BATTERY
Capacity
Ah capacity of the Battery.
Recharge Mode
Recharge type of the Battery
-
Normal
Sealed Battery (VRLA), NiCd without boost-
charge and Open Battery without boost-
charge.
-
NiCd
Nickel Cadmium Battery with boost-charge.
-
Wet Lead Acid Boost
Open Battery with boost-charge.
Float Voltage
Voltage to maintain Battery Charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for
confirmation):
Sealed Battery (VRLA)
:
2.27Vdc for cell
240÷264 cells x 2.27Vdc =
545
÷
600Vdc
NiCd Battery without boost-charge
:
1.41Vdc for cell
386÷424 cells x 1.41Vdc =
545
÷
600Vdc
NiCd Battery with boost-charge
:
1.41 (1.55 boost-charge) Vdc for cell
386 cells x 1.41Vdc =
545
(600)
Vdc
Open Battery without boost-charge
:
2.23Vdc for cell
244÷268 cells x 2.23Vdc =
545
÷
600Vdc
Open Battery with boost-charge
:
2.23 (2.35 boost-charge) Vdc for cell
244÷254 cells x 2.23Vdc =
545
(573) ÷
566
(600)
Vdc
Recharge Current
Maximum Battery Recharge Current.
Max 20% of battery capacity (Ah).
Example: 600Ah
–
max. recharging current 120A.
Stop Operation Time
Residual Battery Autonomy time before UPS forced shut-down.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes.
Cells
Number of cells of the Battery, see “
Float voltage
”.
Example: 240 battery cells
-
40 blocks / 12Vdc Battery
-
80 blocks / 6Vdc Battery
-
240 blocks / 2Vdc Battery
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the
Battery
Manufacturer
.