Liebert GXT2-10KIPPCBL
Quick-Start Guide
Warnings
& Cautions
This input power cable
must be installed only
by properly trained and
qualified personnel.
Opening or removing
the cover of the UPS
may expose you to lethal
voltages within this unit
even when it is appar-
ently not operating and
the input wiring is dis-
connected from the elec-
trical source. Observe all
cautions and warnings
in this quick-start guide
and in the user manual
for the UPS, available
at the Liebert Web site,
www.liebert.com
Failure to do so may re-
sult in serious injury or
death.
Disconnect the Liebert GXT2-10000RT208™ from all electri-
1.
cal inputs.
Remove the top cover from the terminal block cover on the
2.
rear of the UPS. Set all screws aside for reinstallation.
Use a screwdriver or similar tool to remove the knockout.
3.
Slip the locknut onto the input power cable.
4.
Thread the input power cable through the knockout hole.
5.
Slip the fixed ring onto the input power cable.
6.
Connect the wires of the input power cable to the input
7.
power terminal block of the UPS according to the labels on
the wires (see Connect cable wires, below).
Each wire must be connected to the corresponding location
8.
on the input side of the terminal block.
Reattach the terminal block cover to the Liebert GXT2-
9.
10000RT208 using screws removed in Step 2.
Leave a small amount of slack in the input power cable
10.
inside the terminal block and secure the cable to the
terminal block with the fixed ring and locknut (see Secure
cable to back cover, below).
Reattach the top cover to the terminal block using screws
11.
removed in Step 2.
Check the voltage of the input power supply to ensure that
12.
it matches the power requirements of the Liebert GXT2-
10000RT208.
If the input power is correct, shut off power to the supply
13.
socket and mate the UPS to the socket.
L2
L1
N
OUTP UT
INP UT
60 Amp Max Branch
Overcurrent Protection
L2
L1
N
L2
L 1
N
N
L2
L1
G
Wires are labeled
Connect cable wires
Secure cable to back cover
Reattach terminal
block cover
®
™