The Liebert GXT3 is shipped with the following items: 

Terminal Block Communication terminals

Compact disc with:

o

Liebert MultiLink®

o

Configuration program

o

User manual (electronic version)

USB cable, one; 2m (6-1/2 ft.) long

Rack handles with mounting hardware

Plastic tower support base, one set

Plastic Bezel

Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance)

If the UPS is intended to be installed in the Tower orientation, locate the support base and spacers then assemble the two 
stand assemblies with an even number of spacers in each assembly.  Insert the UPS between the support base 
assemblies with adequate space between the assemblies as shown in the picture below.  

Note the display should be 

located on the upper half of the unit in the Tower orientation.  To rotate the display with the bezels removed, depress the 
grooved tabs on the sides and rotate it 90 degrees clockwise.

  If the USP is to be installed in a rack enclosure, follow the 

instructions provided with the rack mounting hardware for proper installation. 

The UPS is cord and plug connected using a L6-30P input plug.  All wiring should be done in accordance to all local and 
national electrical codes.   

The UPS is equipped with output receptacles; connect the equipment to be protected to the output receptacles. 

The GXT3-6000RTL630 is compatible with IT Power Systems.  To configure the unit for operation on the IT Power 
system, remove the 2 screws securing the cover plate in the lower right hand side on the rear of the unit and disconnect 
the jumper, then replace the cover and secure with the screws. 

IT Power System 

Connector 

(with cover removed) 

DISCONTINUED

Summary of Contents for Liebert GXT3 6000VA RTL630

Page 1: ...cture below Note the display should be located on the upper half of the unit in the Tower orientation To rotate the display with the bezels removed depress the grooved tabs on the sides and rotate it 90 degrees clockwise If the USP is to be installed in a rack enclosure follow the instructions provided with the rack mounting hardware for proper installation The UPS is cord and plug connected using...

Page 2: ...n step 1 5 Locate the plastic bezel from the shipping box and attach the bezel to the UPS taking care to align the fastening clips on both ends before inserting them into the holes 6 If your application requires the use of external battery cabinets for longer back up time requirements connect the first battery cabinet to the UPS with the cable provided with the battery cabinet Note it does not mat...

Page 3: ...XT3 UPS has customizable settings that might be required depending on the application Please review the CD that ships with the UPS unit for the steps to use the configuration program and make any necessary changes Once that is complete proceed to the next step 7 Close all output breakers on the rear of the UPS 8 If external battery cabinets are used close all breakers on the rear of each battery c...

Page 4: ...onditions and battery charger failure and continuous alarm A C UPS failed battery test 2 second beep every 60 seconds A D Maintenance bypass switch on continuous A E Bypass feedback 1 second beep every 4 seconds B C REPO one quarter second beep at quarter second intervals B E Short circuit on the output C E UPS shutdown by command from communication USB or Liebert IntelliSlot port no audible alarm...

Reviews: