469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
The event recorder stores motor and system information each time an event occurs. An
event description is stored along with a time and date stamp for troubleshooting purposes.
Events include all trips, any alarm optionally (except Service Alarm, and 469 Not Inserted
Alarm, which always records as events), loss of control power, application of control power,
emergency restarts, and motor starts when a blocking function is active. The latter event
could occur if the block start contacts were shorted out to bypass the 469 and start the
motor.
EVENT 01
is the most recent event and
EVENT 256
is the oldest event. Each new event
bumps the other event records up one until
EVENT 256
is reached. The event record in
EVENT 256
is lost when a new event occurs. This information can be cleared using the
S1 469
SETUP
CLEAR DATA
CLEAR EVENT RECORD
settings.
MESSAGE
TORQUE
EVENT01: 0.0 Nm
Range: 0 to 999999.9. Seen only if
Torque Metering is Enabled
MESSAGE
ANALOG I/P 1
EVENT01: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 1 is Disabled.
MESSAGE
ANALOG I/P 2
EVENT01: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 2 is Disabled.
MESSAGE
ANALOG I/P 3
EVENT01: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 3 is Disabled.
MESSAGE
ANALOG I/P 4
EVENT01: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 4 is Disabled.
Table 6–3: Cause of Events (Sheet 1 of 2)
TRIPS
Acceleration Trip
Analog Diff 1-2 Trip
Analog Diff 3-4 Trip
Analog I/P 1 Trip
Analog I/P 2 Trip
Analog I/P 3 Trip
Analog I/P 4 Trip
Current U/B Trip
Differential Trip
General Sw.A Trip
General Sw.B Trip
General Sw.C Trip
General Sw.D Trip
Ground Fault Backup
Ground Fault Trip
Incomplete Seq Trip
Load Shed Trip
Mechanical Jam Trip
Overload Trip
Overvoltage Trip
Phase Reversal Trip
Power Factor Trip
Pressure Sw. Trip
Reactive Power Trip
Remote Trip
Reverse Power Trip
RTD 1 Trip
RTD 2 Trip
RTD 3 Trip
RTD 4 Trip
RTD 5 Trip
RTD 6 Trip
RTD 7 Trip
RTD 8 Trip
RTD 9 Trip
RTD 10 Trip
RTD 11 Trip
RTD 12 Trip
Short Circuit Backup
Short Circuit Trip
Single Phasing (Unbalanced) Speed Switch Trip
Tachometer Trip
Undercurrent Trip
Underpower Trip
Undervoltage Trip
Vibration Sw.Trip
Volt. Frequency Trip
Loss of Comms Trip
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...