CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–75
RTDs 7 through 10 default to “Bearing” RTD type. There are individual alarm and trip
configurations for each RTD. This allows one of the RTDs to be turned off if it malfunctions.
The alarm level, high alarm level and the trip level are normally set slightly above the
normal running temperature, but below the bearing temperature rating. Trip voting has
been added for extra reliability in the event of RTD malfunction. If enabled, a second RTD
must also exceed the trip temperature of the RTD being checked before a trip will be
issued. If the RTD is chosen to vote with itself, the voting feature is disabled. Each RTD
name may be changed if desired.
5.9.4
RTD 11
PATH: SETTINGS
S8 RTD TEMPERATURE
RTD #11
RTD 11 defaults to “Other” RTD type. The Other selection allows the RTD to be used to
monitor any temperature that might be required, either for a process or additional
bearings or other. There are individual alarm, high alarm and trip configurations for this
RTD #11
[
]
RTD #11 APPLICATION:
Other
Range: Stator, Bearing, Ambient, Other,
None
MESSAGE
RTD #11 NAME:
Range: 8 alphanumeric characters
MESSAGE
RTD #11 ALARM:
Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
MESSAGE
RTD #11 ALARM
TEMPERATURE: 80°C
Range: 1 to 250°C in steps of 1
MESSAGE
RTD #7 HIGH ALARM:
Off
Range: Off, Latched, Unlatched
MESSAGE
HIGH ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
MESSAGE
RTD #11 HIGH ALARM
TEMPERATURE: 80°C
Range: 1 to 250°C in steps of 1
MESSAGE
RTD #11 ALARM
EVENTS: Off
Range: On, Off
MESSAGE
RTD #11 TRIP:
Off
Range: Off, Latched, Unlatched
MESSAGE
RTD #11 TRIP VOTING:
RTD #11
Range: RTD #1 to RTD #12
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
MESSAGE
RTD #11 TRIP
TEMPERATURE: 90°C
Range: 1 to 250°C in steps of 1
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...