CHAPTER 4: INTERFACES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
4–37
NOTE
Note
Cycling power to the relay is recommended after a firmware upgrade.
After successfully updating the 469 firmware, the relay will not be in service and will
require settings programming. To communicate with the relay, the following settings will
have to me manually programmed.
MODBUS COMMUNICATION ADDRESS
BAUD RATE
PARITY
(if applicable)
When communications is established, the saved settings must be reloaded back into the
relay. See
on page 4–33 for details.
Modbus addresses assigned to firmware modules, features, settings, and corresponding
data items (i.e. default values, min/max values, data type, and item size) may change
slightly from version to version of firmware. Refer to GEK-106491C:
469 Communications
Guide.
The addresses are rearranged when new features are added or existing features are
enhanced or modified. The
EEPROM DATA ERROR
message displayed after upgrading/
downgrading the firmware is a resettable, self-test message intended to inform users that
the Modbus addresses have changed with the upgraded firmware. This message does not
signal any problems when appearing after firmware upgrades.
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...