CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–13
Enter the dedicated MAC ID and baud rate as per the DeviceNet design (Refer to GEK-
106491C:
469 Communications Guide)
. The DeviceNet option is implemented by the 469
relay using the AnyBus-S DeviceNet (HMS) module as a communication adapter. The
module is ODVA certified and acts as a server between the relay and the DeviceNet
network.
The following master/slave connection objects are supported by the 469 DeviceNet
implementation:
• Explicit Messaging Connection
• Poll I/O Connection
• Change of State or Cyclic I/O Connection
The following objects have been implemented:
Refer to publication GEK-106491C:
469 Communications Guide
for additional details
on the DeviceNet implementation.
5.2.4
Real Time Clock
PATH: SETTINGS
S1 469 SETUP
REAL TIME CLOCK
The correct time and date must be entered for event recorder events to be correctly time/
date stamped. A supercap backed internal clock runs for 45 days even when power is off. It
has an accuracy of approximately ±5 minutes per month. It must be periodically corrected
manually through the front panel or via the RS485 serial link clock update command. If the
approximate time an event occurred without synchronization to other relays is sufficient,
then entry of time/date from the front panel keys is adequate.
If the RS485 serial communication link is used, then all the relays can keep synchronized
time. A new clock time is pre-loaded into the 469 memory via the RS485 port by a remote
computer to each relay connected on the communications channel. After the computer
broadcasts (address 0) a “set clock” command, all relays in the system begin timing at the
same instant. There can be up to 100 ms of delay in receiving serial commands so the
Object
Class
DeviceNet objects
Identity object
01h
Message Router object
02h
DeviceNet object
03h
Assembly object
04h
Connection object
05h
Acknowledge Handler object
2Bh
469 specific objects
I/O Data Input Mapping object
A0h
Parameter Data Input Mapping object
B0h
REAL TIME
[
]
CLOCK
DATE (MM.DD.YYYY)
01/01/1994
Range: 01 to 12 / 01 to 31 / 1995 to
2094
MESSAGE
TIME (HH.MM.SS):
12:00:00
Range: 00 to 23 hrs / 00 to 59 min. / 00
to 59 sec.
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...