6–14
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
6.3.5
Power Metering
PATH: ACTUAL VALUES
A2 METERING DATA
POWER METERING
The values for power metering and 3-phase total power quantities are displayed here.
Watthours and varhours can also be seen here.
NOTE
Note
An induction motor by convention consumes Watts and vars (+Watts and +vars). A
synchronous motor can generate vars (–vars) and feed them back to the power system.
If the
S2 SYSTEM SETUP
VOLTAGE SENSING
VOLTAGE TRANSFORMER RATIO
settings is
not programmed, the
THIS FEATURE NOT PROGRAMMED
flash message appears when
an attempt is made to enter this group of messages.
NOTE
Note
Real Power (hp) is converted directly from Real Power (kW). This display-only value is not
used for protection functions. This message will not display more than 65535 hp regardless
of the actual kW that are being metered.
POWER
[
]
METERING
POWER FACTOR:
0.00
Range: 0.01 to 0.99 Lead or Lag, 0.00,
1.00
MESSAGE
REAL POWER:
0 kW
Range: 0 to ±99999 kW
MESSAGE
REAL POWER:
O hp
Range: 0 to 65535 hp
MESSAGE
REACTIVE POWER:
0 kvar
Range: 0 to ±99999 kvar
MESSAGE
APPARENT POWER:
0 kVA
Range: 0 to 65535 kVA
MESSAGE
POSITIVE WATTHOURS:
0.000 MWh
Range: 0.000 to 999999.999 MWh
MESSAGE
POSITIVE VARHOURS:
0.000 Mvarh
Range: 0.000 to 999999.999 Mvarh
MESSAGE
NEGATIVE VARHOURS:
0.000 Mvarh
Range: 0.000 to 999999.999 Mvarh
MESSAGE
TORQUE:
000.0 Nm
Range: 0.00 to 999999.9 Nm. Seen only
if torque metering is enabled
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...