5–70
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
•
Max. Starts/Hour Permissible
: A motor start is assumed to be occurring when the
469 measures the transition of no motor current to some value of motor current. At
this point, one of the Starts/Hour timers is loaded with 60 minutes. Even unsuccessful
start attempts will be logged as starts for this feature. Once the motor is stopped, the
number of starts within the past hour is compared to the number of starts allowable. If
the two numbers are the same, a block will occur. If a block occurs, the lockout time
will be equal to the longest time elapsed since a start within the past hour, subtracted
from one hour.
For example, if
MAX. STARTS/HOUR PERMISSIBLE
is programmed at “2”,
–
one start occurs at T = 0 minutes,
–
a second start occurs at T = 17 minutes,
–
the motor is stopped at T = 33 minutes,
–
a block occurs,
–
the lockout time would be 1 hour – 33 minutes = 27 minutes.
•
Time Between Starts Permissible
: A motor start is assumed to be occurring when the
469 measures the transition of no motor current to some value of motor current. At
this point, the Time Between Starts timer is loaded with the entered time. Even
unsuccessful start attempts will be logged as starts for this feature. Once the motor is
stopped, if the time elapsed since the most recent start is less than the
TIME BETWEEN
STARTS PERMISSIBLE
settings, a block will occur. If a block occurs, the lockout time will
be equal to the time elapsed since the most recent start subtracted from the
TIME
BETWEEN STARTS PERMISSIBLE
. A value of “0” effectively disables this element.
For example, if
TIME BETWEEN STARTS PERMISSIBLE
is programmed = 25 min.
–
a start occurs at T = 0 minutes,
–
the motor is stopped at T = 12 minutes,
–
a block occurs,
–
the lockout time would be 25 minutes – 12 minutes = 13 minutes
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...