CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–23
FIGURE 5–1: Reduced Voltage Start Contactor Control Circuit
FIGURE 5–2: Reduced Voltage Starting Current Characteristic
NOTE
Note
If this feature is used, the Starter Status Switch input must be either from a common
control contact or a parallel combination of Auxiliary ‘a’ contacts or a series combination
of Auxiliary ‘b’ contacts from the reduced voltage contactor and the full voltage contactor.
Once transition is initiated, the 469 assumes the motor is still running for at least 2
seconds. This prevents the 469 from recognizing an additional start if motor current goes
to zero during an open transition.
808
7
24A2.CDR
CC1
CC2
46
9
BLO
CK
T
RI
P
STOP
ST
AR
T
RED
U
CED
VOLT
A
G
E
C
O
N
T
AC
TO
R
F
ULL VOLT
A
G
E
C
O
N
T
AC
TO
R
CC1
S
EA
L
IN
46
9
3 A
U
X
CC2
S
EA
L
IN
808725A1.CDR
MOTOR
AMPS
(% FLA)
When the currrent falls below
the Transition Level and/or the
Timer expires, the Auxiliary
Relay activates for 1 second
Transition Time
TIME
signifies
Open Transition
3 x FLA
Transition
Level
FLA
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...