CHAPTER 6: ACTUAL VALUES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
6–17
FIGURE 6–1: Vector display in EnerVista 469 Setup
IEEE conventions define vectors in terms of relative angles as shown below:
FIGURE 6–2: Flow Direction of Signed Values for Watts and Vars
All phasors calculated by 469 relays are rotating phasors that maintain the correct phase
angle relationships with each other at all times.
For display purposes, all phasor angles in a given relay are referred to phase Van or Vab,
depending on the
S2 SYSTEM SETUP
VOLTAGE SENSING
VT CONNECTION TYPE
settings.
If set to “Wye”, the reference quantity is Van; if set to “Open Delta”, the reference quantity is
Vab. If neither voltage is available, the relay uses the current in Phase A as reference.
The phase angles are assigned and displayed as positive angles. However, by design, the
relay will always work with angles in the lagging direction. This is illustrated below.
806558A1.CDR
Ia
Van
Phase
R
otat
i
on
Vab
Vcn
Vbn
Ic
Vca
Ib
Vbc
46
9
R
e
l
ay
Vo
l
tage
C
urrent
W
A
TTS
=
Pos
i
t
i
ve
V
AR
S
=
Pos
i
t
i
ve
P
F =
Lag
M
G
Source
Load
F
°
La
g
P
ER IEEE C
O
N
V
EN
T
I
O
N
S
P
ARA
M
E
T
ER
S
A
S S
EEN
B
Y
T
HE 46
9
RE
L
AY
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...