5–30
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Pressure Switch Alarm
PATH: SETTINGS
S3 DIGITAL INPUTS
ASSIGNABLE INPUT 1(4)
These settings apply only if the
INPUT 1(4) FUNCTION
is “Pressure Sw. Alarm”.
Once the pressure switch alarm function is chosen for one of the assignable digital inputs,
the settings messages shown here will follow the assignment message. The Pressure
Switch alarm feature may be blocked for a specified period of time from a motor start. A
value of zero for the block time indicates that the feature is always active, when the motor
is stopped or running. After the block delay has expired, the digital input will be monitored.
If a closure occurs, after the specified delay, an alarm will occur.
Pressure Switch Trip
PATH: SETTINGS
S3 DIGITAL INPUTS
ASSIGNABLE INPUT 1(4)
These settings apply only if the
INPUT 1(4) FUNCTION
is “Pressure Switch Trip”.
Once the Pressure Switch Trip function is chosen for one of the digital inputs, the settings
messages shown here will follow the assignment message. The Pressure Switch Trip
feature may be blocked for a specified period of time from a motor start. A value of zero for
the Block time indicates that the feature is always active, when the motor is stopped or
running. After the block delay has expired, the digital input will be monitored. If a closure
occurs, after the specified delay, a trip will occur.
ASSIGNABLE [
]
INPUT 1
INPUT 1 FUNCTION:
Pressure Sw Alarm
Range: See above
MESSAGE
BLOCK PRES. SW. ALARM
FROM START: 0 s
Range: 0 to 5000 s in steps of 1
MESSAGE
PRESSURE SWITCH
ALARM: Unlatched
Range: Latched, Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Auxiliary2 & Aux3,
Alarm & Auxiliary3, Auxiliary2,
Aux2 & Aux3, Auxiliary3, None
MESSAGE
PRESSURE SW. ALARM
DELAY: 5.0 s
Range: 0.1 to 100.0 sec., step: 0.1
MESSAGE
PRESSURE SW. ALARM
EVENTS: Off
Range: On, Off
ASSIGNABLE [
]
INPUT 1
INPUT 1 FUNCTION:
Pressure Switch Trip
Range: See above
MESSAGE
BLOCK PRES. SW. TRIP
FROM START: 0 s
Range: 0 to 5000 sec.; step: 1
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
MESSAGE
PRESSURE SW. TRIP
DELAY: 5.0 s
Range: 0.1 to 100.0 s in steps of 0.1
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...