CHAPTER 6: ACTUAL VALUES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
6–13
6.3.3
Voltage Metering
PATH: ACTUAL VALUES
A2 METERING DATA
VOLTAGE METERING
Measured voltage parameters will be displayed here.
If no VT connection type is programmed for the
S2 SYSTEM SETUP
VOLTAGE SENSING
VT CONNECTION TYPE
settings, the
THIS FEATURE NOT PROGRAMMED
flash
message will appear when an attempt is made to enter this group of messages.
6.3.4
Speed
PATH: ACTUAL VALUES
A2 METERING DATA
SPEED
If the Tachometer function is assigned to one of the digital inputs, the tachometer readout
may be viewed here.
If no digital input is configured as tachometer in
S3 DIGITAL INPUTS
ASSIGNABLE
INPUT1(4)
, the
THIS FEATURE NOT PROGRAMMED
flash message will appear when an
attempt is made to enter this group of messages.
VOLTAGE
[
]
METERING
Vab:
0
Vbc:
0
Vca:
0
Volts
Range: 0 to 20000 V. Not seen if VT
Connection is set as None
MESSAGE
AVERAGE LINE
VOLTAGE: 0 Volts
Range: 0 to 20000 V. Not seen if VT
Connection is set as None
MESSAGE
Van:
0
Vbn:
0
Vcn:
0
Volts
Range: 0 to 20000 V. Seen only if VT
Connection is set as Wye
MESSAGE
AVERAGE PHASE
VOLTAGE: 0 Volts
Range: 0 to 20000 V. Seen only if VT
Connection is set as Wye
MESSAGE
SYSTEM FREQUENCY:
0.00 Hz
Range: 0.00, 20.00 to 120.00 Hz
SPEED
[
]
TACHOMETER
0 RPM
Range: 0 to 7200 RPM
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...