4–4
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES
4.1.5
Keypad
Description
The 469 display messages are organized into main menus, pages, and sub-pages. There
are three main menus labeled settings, Actual Values, and Target Messages.
Pressing the
MENU
key followed by the
MESSAGE
key scrolls through the three main
menu headers, which appear in sequence as follows:
Pressing the
MESSAGE
key or the
ENTER
key from these main menu pages will display
the corresponding menu page. Use the
MESSAGE
and
MESSAGE
keys to scroll
through the page headers.
When the display shows
SETTINGS
, pressing the
MESSAGE
key or the
ENTER
key will
display the page headers of programmable parameters (referred to as settings in the
manual). When the display shows
ACTUAL VALUES
, pressing the
MESSAGE
key or the
ENTER
key displays the page headers of measured parameters (referred to as actual
values in the manual). When the display shows
TARGET MESSAGES
, pressing the
MESSAGE
key or the
ENTER
key displays the page headers of event messages or alarm
conditions.
Each page is broken down further into logical sub-pages. The
MESSAGE
and
MESSAGE
keys are used to navigate through the sub-pages. A summary of the settings
and actual values can be found in the chapters 5 and 6, respectively.
The
ENTER
key is dual purpose. It is used to enter the sub-pages and to store altered
settings values into memory to complete the change. The
MESSAGE
key can also be
used to enter sub-pages but not to store altered settings.
The
ESCAPE
key is also dual purpose. It is used to exit the sub-pages and to cancel a
settings change. The
MESSAGE
key can also be used to exit sub-pages and to cancel
settings changes.
The
VALUE
keys are used to scroll through the possible choices of an enumerated settings.
They also decrement and increment numerical settings. Numerical settings may also be
entered through the numeric keypad.
Pressing the
HELP
key displays context-sensitive information about settings such as the
range of values and the method of changing the settings. Help messages will
automatically scroll through all messages currently appropriate.
The
RESET
key resets any latched conditions that are not presently active. This includes
resetting latched output relays, latched Trip LEDs, breaker operation failure, and trip coil
failure.
1. SETPOINTS
Press [
] for more
2. ACTUAL VALUES
Press [
] for more
3. TARGET MESSAGES
Press [
] for more
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...