CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–13
To set the ground CT ratings, modify the
S2 SYSTEM SETUP
CURRENT SENSING
GROUND
CT
and the
S2 SYSTEM SETUP
CURRENT SENSING
GROUND CT PRIMARY
settings as
shown below.
Press the
MENU
key until the relay displays the Setpoints menu
header.
1. SETPOINTS
Press [
] for more
Press
MESSAGE
or
ENTER
SETPOINTS
[
]
S1 469 SETUP
Press
MESSAGE
SETPOINTS
[
]
S2 SYSTEM SETUP
Press
MESSAGE
or
ENTER
CURRENT
[
]
SENSING
Press
MESSAGE
or
ENTER
PHASE CT PRIMARY:
600 A
Press
MESSAGE
MOTOR FULL LOAD AMPS
FLA: 318 A
Press
MESSAGE
GROUND CT:
50:0.025
Press the
VALUE
keys until
“5 A Secondary” is displayed.
GROUND CT:
5 A Secondary
Press the
ENTER
key to store the settings.
NEW SETPOINT HAS
BEEN STORED
Press
MESSAGE
GROUND CT PRIMARY:
100 A
Press the
VALUE
keys until 50 A is displayed, or
enter the value directly via the numeric
keypad.
GROUND CT PRIMARY:
50 A
Press the
ENTER
key to store the settings.
NEW SETPOINT HAS
BEEN STORED
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...