5–20
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
PHASE CT PRIMARY: “
350”
MOTOR FULL LOAD AMPS:
“330”
GROUND CT:
“50:0.025”
5.3.2
Voltage Sensing
PATH: SETTINGS
S2 SYSTEM SETUP
VOLTAGE SENSING
The manner in which the voltage transformers are connected must be entered here. A
value of “None” for
VT CONNECTION TYPE
indicates that no voltage measurement is
required. Note that phase reversal is disabled for single VT operation. All voltages are
assumed balanced. Also, frequency is only available for AN or AB connections.
The
ENABLE SINGLE VT OPERATION
settings is seen only if the
VT CONNECTION TYPE
is
“Open Delta” or “Wye”.
If voltage measurements are to be made, the turns ratio of the voltage transformers must
be entered. The
VOLTAGE TRANSFORMER RATIO
must be chosen such that the secondary
voltage of the VTs is between 40 and 240 V when the primary is at
MOTOR NAMEPLATE
VOLTAGE
. All voltage protection features that require a level settings are programmed as a
percent of the
MOTOR NAMEPLATE VOLTAGE
or rated voltage, where
MOTOR NAMEPLATE
VOLTAGE
represents the rated design voltage line to line.
For example, given the motor nameplate voltage as 4160 V and the VTs are 4160/120
Open Delta, set the voltage sensing settings as follows:
VT CONNECTION TYPE:
“Open Delta”
VT RATIO:
“34.67:1”
MOTOR NAMEPLATE VOLTAGE:
“4160”
5.3.3
Power System
PATH: SETTINGS
S2 SYSTEM SETUP
POWER SYSTEM
VOLTAGE
[
]
SENSING
VT CONNECTION TYPE:
None
Range: Open Delta, Wye, None
MESSAGE
ENABLE SINGLE VT
OPERATION: OFF
Range: AN, BN, CN, OFF or AB, BC, OFF
MESSAGE
VOLTAGE TRANSFORMER
RATIO: 35.00:1
Range: 1.00:1 to 300.00:1 in steps of
0.01
MESSAGE
MOTOR NAMEPLATE
VOLTAGE: 4000 V
Range: 100 to 36000 V in steps of 1
POWER
[
]
SYSTEM
NOMINAL SYSTEM
FREQUENCY: 60 Hz
Range: 50 Hz, 60 Hz, Variable
MESSAGE
SYSTEM PHASE
SEQUENCE: ABC
Range: ABC, ACB
MESSAGE
SPEED2 PHASE
SEQUENCE: ABC
Range: ABC, ACB
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...