5-52
F35 MULTIPLE FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
DNP VOLTAGE SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
DNP POWER SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
DNP ENERGY SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
DNP PF SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
DNP OTHER SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
DNP CURRENT DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
DNP VOLTAGE DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
DNP POWER DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
DNP ENERGY DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
DNP PF DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
DNP OTHER DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
DNP TIME SYNC IIN
PERIOD: 1440 min
Range: 1 to 10080 min. in steps of 1
DNP MESSAGE FRAGMENT
SIZE: 240
Range: 30 to 2048 in steps of 1
DNP OBJECT 1
DEFAULT VARIATION: 2
Range: 1, 2
DNP OBJECT 2
DEFAULT VARIATION: 2
Range: 1, 2, 3
DNP OBJECT 20
DEFAULT VARIATION: 1
Range: 1, 2, 5, 6
DNP OBJECT 21
DEFAULT VARIATION: 1
Range: 1, 2, 9, 10
DNP OBJECT 22
DEFAULT VARIATION: 1
Range: 1, 2, 5, 6
DNP OBJECT 23
DEFAULT VARIATION: 1
Range: 1, 2, 5, 6
DNP OBJECT 30
DEFAULT VARIATION: 1
Range: 1, 2, 3, 4, 5
DNP OBJECT 32
DEFAULT VARIATION: 1
Range: 1, 2, 3, 4, 5, 7
DNP NUMBER OF PAIRED
CONTROL POINTS: 0
Range: 0 to 32 in steps of 1
DNP TCP CONNECTION
TIMEOUT: 120 s
Range: 10 to 7200 s in steps of 1
DNP EVENT TIME BASE:
LOCAL
Range: UTC, LOCAL