5-36
F35 MULTIPLE FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Figure 5-11: Annunciator editor with preview shown
Reset
Range: ON, OFF, any FlexLogic operand
Default: OFF
This setting selects a FlexLogic operand that when activated acknowledges/resets all annunciator windows in the
graphical front panel. This setting is the same as the one defined in
Settings > Inputs/Outputs > Resetting > Reset
Annunciator
; see the Resetting section in this chapter.
LAYOUT
Range: 3x4, 4x6, 6x8
Default: 3x4
Selects the number of rows and columns to display on the annunciator pages. For example, 3x4 means 12 windows
display per page over eight pages. Up to 96 entries are possible.
To view the layout, click the
Preview
button.
PAGE NAMES
Range: up to 20 alphanumeric characters
Default: Page 1...Page 8
Up to 20 characters can be input as the name of each annunciator page. The number of pages depends on the Layout.