5-64
F35 MULTIPLE FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
download. Incrementing occurs whether or not the setting is represented in the information model. When a UR device or
EnerVista UR Setup accepts an SCL file, paramRev is set to the value in that SCL file. When EnerVista UR Setup changes
one or more settings, and prepares an SCL file, it increments paramRev to the next higher multiple of 10 000.
In the right pane, logical nodes assigned permanently to the Master logical device and LLN0 in all logical devices are
greyed-out as shown earlier. These are not movable. Any other logical node can be dragged to any of the logical devices in
the middle pane, which causes that logical device to be re-assigned to that logical device. Right-clicking a logical node
device displays a menu that lists the logical devices that this logical node can be moved to. Clicking one of these re-assigns
the logical node. Other common keyboard and/or mouse action can be used to select one or more logical nodes and move
the selected nodes together.
Figure 5-26: Move logical node
GOOSE
The path is
Settings > Product Setup > Communications > IEC 61850 > GOOSE
.
Support for Routable GOOSE
Routable GOOSE (R-GOOSE) is supported in firmware release 7.4 and later. Routable GOOSE allows UR and other devices to
be located in separate networks. Encryption/decryption of messages is performed by a separate gateway device.
Messages are routed using a separate router, using IP addresses.
Note the following behavior:
•
A v7.4 device can send an R-GOOSE message to another v7.4 device when both have R-GOOSE active as the protocol
•
A v7.4 device can send a GOOSE message to another v7.4 device when both have GOOSE active as the protocol
Each logical device has a name: LDName. (Note the upper case LD.) LDName has both a product-related form and
a function-related form as per IEC 61850 6:2009 8.5.3.
SCL files invariably use the product-related form of LDName. The product-related form is the concatenation of the
IED name of the device and the individual logical device's inst name. The IED name is the value of the "IED NAME"
setting on the Server Configuration panel, and the logical device inst names are each the value of the
corresponding "Product LD inst name" setting here. The "Product LD inst name" of the first logical device is fixed at
"Master".
Communications use the function-related form of LDName if a function-related name is defined, otherwise
communications use the product-related name. The function-related name is the value of the corresponding
"Functional ldName" setting if this setting is not empty, if empty the function-related name is not defined.
In SCL, the function-related name is specified by the LDevice element attribute ldName (note the lower case ld).
Absence of this attribute indicates the function-related name is not defined. In SCL the product-related name is
specified by the name attribute of the IED element and the inst attribute of the LDevice element.