5-132
F35 MULTIPLE FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
FltRptRFLO1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo"
here is select-before-operate. Enhanced security means that the F35 reports to the client the breaker 1 position at the
end of the command sequence.
LLN0.EvtRcdClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR EVENT RECORDS.
LPHD1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR ALL RELAY RECORDS.
OscRDRE1.RcdTrg.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command FORCE TRIGGER.
OscRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR OSCILLOGRAPHY.
DatLogRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR DATA LOGGER.
CBArc0SCBR1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
DmdMtrMMTR1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
EnrMtrMMTR1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
GGIO1
GGIO1 is a UR feature that allows up to 128 UR FlexLogic operands to be user-mapped to IEC 61850 information model
data attributes.
For the value of a FlexLogic operand to be read via MMS, included in TxGOOSE messages, or included in buffered/
unbuffered reports, the value must be assigned to a data attribute. GGIO1 allows those FlexLogic operands that have not
yet been factory-assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their values
included in IEC 61850 communications.
Navigate to
Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO1
to access the settings for GGIO1.