Start-Up Failure
RAM check, NVRAM check,
Application checksum, or BootROM
checksum failed during system start-
up
Use WESMAINT II+ to
view the error message.
System Shut Down
RAM, NVRAM, FLASH, or BootROM
internal system diagnostics failed
Use WESMAINT II+ to
view the error message.
Only the System
Monitor is Running
No valid application code is
detected.
Load application code.
Code Download
Failure
Download interrupted or data error
encountered in downloaded file.
Baud rate set too high.
Clear Flash EPROM
memory. Restart
download procedure.
Reduce baud rate to
19200 or less.
Cannot Download
Code
Logged into the Application Monitor
Exit Application Monitor,
and launch System
Monitor
Note:
When using a D25 with a High Current Control Card (P/N 517-0492)
installed, also consult the ‘Using the Current-Monitoring Digital Outputs’ for
further details on rules regarding current monitoring and current seal-in.
Initialization Errors
Overview
The normal case is that the configuration and code in the Boot file match
those in the memory of the client, thus causing the client to initialize
immediately.
However, several error situations related to initialization can occur with file
transfers.
Symptom
Possible Causes
Suggestions
BootROM Error
Corrupted or incorrect configuration
loaded in NVRAM
Press ‘y’ during boot up to
enter D25 system monitor,
then download
configuration.
TFTP ERROR
Configuration was not completed or
data corruption has occurred at the
server
Use WESMAINT II+ to
view the error message.
Applications Not
Enabled
Configuration was not completed or
data corruption has occurred at the
server
Use WESMAINT II+ to
view the error message.
System Restarts
Data download failure
Use WESMAINT II+ to
view the error message.
Only diagnostic input
can be entered
No configuration is detected in either
NVRAM or in EPROM on start-up
Download a configuration
remotely via the system
monitor, and reboot
System error
No configuration is detected in either
NVRAM or in EPROM on start-up
Download a configuration
remotely via the system
monitor, and reboot