GE Grid Solutions
D25
User's Manual
GE Information
994-0081-3.00-21
119
Main Board,
Continued
Type III WESDAC board jumpers and their functions:
Board Layout
Drawing
Table: Jumper
Settings
Type III WESDAC board jumper settings.
Jumper
Function
Default Setting
P5
Factory use only
JTAG Connector, Do Not Jumper
P6
Factory use only
BDM Connector, Do Not Jumper
JP1
Factory use only, jumper 5 –
6 to enable JTAG for
programming FLASH or
EPLD
No Jumpers on any pins
JP2
Selects EPROM size, and
allows for different FLASH
memory options
Pins 3 – 5 shorted: 256K EPROM
Pins 5 – 7 shorted: 512K EPROM
Backward
Compatibility
Jumpers
The following table shows the jumper setting for backward compatibility.
These jumpers cannot set the wetting voltage source of the CE Mark
digital input cards.
(The wetting voltage must be routed externally for the
CE Mark cards.)
JP3
Wetting for Low Voltage DI
card #1
Pin 3 – 5 and 4 – 6 shorted: External or
D25 power supply
Pins 3 – 4 shorted: Voltage Sense
Note:
These jumpers not used with
High Voltage DI Cards
JP4
Wetting for Low Voltage DI
card #2
JP5
Wetting for Low Voltage DI
card #3
Reset Switch
The Type III WESDAC board does not have a “slide” reset switch.
JP2
JP1
P6
BDM
P5
JTAG
JP5
JP4
JP3
Summary of Contents for D25
Page 170: ......