Downloading a Configuration,
Continued
Procedure: Download Files
(continued)
Step
Action
11
Type
Y
and press
ENTER
at the
Do you wish to proceed?
prompt
(not case-sensitive)
Result: The system automatically verifies that Flash EPROM
memory has been cleared.
The
D25S>
prompt appears. The download can be
started.
Optional Step 1: Speed-up communication to shorten download time.
•
Changing the speed to a higher rate may increase the probability of a
communication error, resulting in failure of the download procedure.
•
Some third-party communication applications may not be capable of
running at these higher speeds reliably.
If you experience either of these limitations, leave the communication
speed at the default value of 9600 bps.
12
Type
Baud 38400
ENTER
(speeds up to 38.4 Kbps, may be chosen
based on ambient EMI, cable length, PC and software limits etc.)
Result: the monitor will now be communicating at 38.4 Kbps
13
Configure the
HyperTerminal
program to communicate at the
same speed, and reconnect to the 68K monitor.
Optional Step 2: Provide feedback during download
14
If the communication software you are using
does not
have any
“progress indicator’, such as
HyperTerminal
, echo can be
enabled to visually display the code file on your monitor as it is
transferred.
This option can be usually found in the communication settings or
properties of the communication program.
Note
: enabling echo may slow transfer slightly.