D25
User's Manual
GE Grid Solutions
114
994-0081-3.00-21
GE Information
Battery Replacement,
Continued
•
Removing the battery when the D25 is powered down results in loss of the
configuration data and any other database information stored in NVRAM.
•
Download the configuration file to restore operation.
•
There are many electrostatically sensitive components near the battery.
•
Extreme caution and proper procedures for servicing electrostatically sensitive
components must be observed.
Recycling of
Batteries
The D25 Lithium battery is recyclable and does not contain mercury, cadmium, or
lead in levels above those regulated by the European Union. Recycle the battery
according to local waste management regulations.
In accordance with European Directive 2006/66/EC, batteries are marked with the
crossed out wheeled bin, which indicates that they cannot be disposed of as unsorted
municipal waste in the European Union. Users of batteries must use the collection
points available to customers for the return, recycling, and treatment of batteries.
Customer participation is important to minimize the negative effects of batteries to
the environment and sustain available natural resources. For more information see
www.weeerohsinfo.com.
Procedure:
Changing
Battery
Changing the battery with power applied:
Step
Action
Battery Removal
1
Using a plastic or other non-conductive tool, pry the black plastic
clip holding the battery away from the battery holder.
2
When free, the battery and clip can be removed together.
3
Remove the clip from the battery, and retain.
Battery Replacement
4
Place good battery into battery holder, carefully noting proper
polarity.
5
Place clip retained during battery removal across the center of the
battery, and press down until it clicks into the retaining notches in
the battery holder.