GE Grid Solutions
D25
User's Manual
GE Information
994-0081-3.00-21
121
Main Board,
Continued
Type III
WESDAC
Wetting
Jumper Detail
(Backward
Compatibility)
Jumpers shown are for the first (top) 32-point module. Jumpers (J4 and J3)
for the other two modules work in the same way.
1
3
5
2
4
6
1
3
5
2
4
6
No Wetting
(Voltage Detect)
External or
Supplied Wetting
.
JP5 JP5
Note
: Supplied wetting voltage is 24 or 48 Volts: depends on power supply
used.
Note
Supplied Wetting option is not available if the Graphics Display panel is
installed.
Procedure:
Board
Replacement
How to replace the WESDAC Board:
Step
Action
1
Hold the mounting brackets at each side of the module.
2
Tilt the card slightly, and insert the top first, ensuring that the
battery connections do not come into contact with the metal
housing.
3
Carefully position the board so that:
−
the alignment pins align with the holes at the top and bottom of
the WESDAC Board
−
the captive screws align with their holes
−
the female connectors on the rear of the WESDAC Board align
with the male connectors of other boards
4
Press the WESDAC Board firmly into position.
5
Tighten
all
the mounting screws to ensure the WESDAC Board
connectors are firmly attached and the board is grounded.
Summary of Contents for D25