Testing Hardware I/O Points,
Continued
Procedure:
Verify Analog
Input (cont’d)
On the Analog Input Display:
Step
Action
5
Press
CTRL
+
G
and type the number of the first input point (if
known), or use the up and down arrow keys to scroll to the desired
analog input point.
6
Connect one end of testing leads to a calibrated voltage or current
source.
7
Connect the other end of the leads to the first analog input point on
the DC analog input termination.
8
Using the following table as a reference, adjust input voltage or
current to these levels:
•
0% of full scale
•
5% of full scale
•
95% of full scale
9
Verify that the values displayed in WESMAINT fall near the
values shown in the following table.
10
Go back to Step 5 and repeat as desired for other points on the DC
analog input termination.
Table: DC
Analog Input
Values
Use this table to verify the DC analog input values.
DC Input
Option
0% FS
Nominal
Displayed
Count
5% FS
Nominal
Displayed
Count
95% FS
Nominal
Displayed
Count
5 V
0 V
0
0.25V
1638
4.75V
31129
1 mA
0 mA
0.05 mA
0.95 mA
5 mA
0 mA
0.25 mA
4.75 mA
10 mA
0 mA
0.50 mA
9.5 mA
20 mA
0 mA
1.0 mA
19 mA
Notes
•
Full-scale for all displayed DC analogs is represented by a range of 32767 to
-32768 (15-bit plus sign value).
•
Full-scale of DC Voltage and Current measurements is the nominal value.