D25
User's Manual
GE Grid Solutions
154
994-0081-3.00-21
GE Information
Electrical Specifications,
Continued
Auxiliary Digital Outputs
Three single digital outputs for System Fail indication, Radio Keying and Auxiliary Digital output
System Fail Relay Contacts
1 Form B (Normally Closed) Relay
Radio keying, and auxiliary relay
1 Form A (Normally Open) Relay
Maximum Switching Voltage
220 V
dc
Minimum Switching Voltage
10 μA, 10 mV
dc
Carry Continuous
2.00 A
Break (DC resistive)
Voltage
Current
24
V
dc
2.00 A
48
V
dc
1.25 A
110
V
dc
0.55 A
125
V
dc
0.48 A
220
V
dc
0.27 A
Operate time
< 4 ms
Max switching speed
20 changes/sec at rated break load
Contact material
Silver (Ag) with Gold (Au) flash
DC Analog Inputs
16 optically isolated differential inputs
Measurement Range
120% of nominal
Overload Voltage
±
30 V
dc
(NM) continuous
±
200 V
dc
(CM) continuous
Nominal Voltage Input Range
±
5 V
dc
Voltage Input Impedance
Greater than 10 MΩ
Nominal Current Input Range
Options
±
1 mA,
±
5 mA,
±
10 mA, or
±
20 mA
Current Input Burden
5k to 250Ω (1 to 20 mA)
AC Analog Measurement
Direct AC analog inputs from CTs and PTs. One to six 3-phase circuits. 15 AC analog inputs
organized in groups of three (3) inputs, transformer isolated
Line Frequency
50/60 Hz, nominal
±
5 Hz
AC Analog Measurement
Direct AC analog inputs from CTs and PTs. One to six 3-phase circuits. 15 AC analog inputs
organized in groups of three (3) inputs, transformer isolated
Line Frequency
50/60 Hz, nominal
±
5 Hz
Summary of Contents for D25
Page 170: ......