GE Information
Testing Hardware I/O Points,
Continued
Digital Input
Verification
Test
Testing Digital Inputs: Digital input changes are displayed in WESMAINT.
Procedure:
Verify Digital
Input
To conduct this test the code and configuration file must be downloaded to
the D25’s FLASH memory.
Note
: The following procedure assumes that the digital inputs for the D25
are configured to use
supplied
wetting. Refer to page 36 for
configuration information.
From the WESMAINT II+
Main Menu
:
Step
Action
1
On the
Main Menu
, type
1
—
System Data Display
.
Results: The
System Data Menu
appears.
2
On the
System Data Menu
, type
1
—
Digital Input Display
.
Results: The point numbers and (optionally) point descriptions
appear on the WESMAINT II+ display.
3
Use the arrow keys to move up or down to highlight the desired
point number.
4
Use a wire jumper to short out the desired input point, and verify
that WESMAINT shows that the point status has changed to On.
5
Go back to Step 3 and repeat the test as necessary to test other
available digital points.