GE Grid Solutions
D25
User's Manual
GE Information
994-0081-3.00-21
45
Control Outputs,
Continued
Table: D25KE
DB-25 Control
Function
Terminal
Block – P1
Phoenix 8-pin terminal block – P1 Pinout:
P1
Pin
Signal
Function
Comments
1
COIL_SUP
Control Voltage
Interposer Relay Coil Power Supply
connections
2
COIL_SUP_R
TN
Control Voltage return
3
JMP1
Relays 1-8 mode
jumper point
Jumper to Pin 1-5 (+VC) for R/L
Jumper to Pin 1-6 (MT) for T/C
4
JMP2
Relays 9-16 mode
jumper point
Jumper to Pin 1-5 (+VC) for R/L
Jumper to Pin 1-6 (MT) for T/C
5
+VC
Control Voltage (fused) Jumper to JMP1 through 4 for R/L
6
MT
Master Trip Bus
Jumper to JMP1 through 4 for T/C
7
JMP3
Relays 17-24 mode
jumper point
Jumper to Pin 1-5 (+VC) for R/L
Jumper to Pin 1-6 (MT) for T/C
8
JMP4
Relays 25-32 mode
jumper point
Jumper to Pin 1-5 (+VC) for R/L
Jumper to Pin 1-6 (MT) for T/C
1 2 3 4 5 6 7 8