GE Grid Solutions
D25
User's Manual
GE Information
994-0081-3.00-21
55
Control Outputs,
Continued
Table: D25KE
FACE-40
Board Control
Optioning
Specific pins of both FACE-40 Connectors, G1 and G2, are used to configure
the D25KE module for trip/close or raise/lower operation: as listed below:
Pin
Signal
Function
Comments
G1 1
COIL_SUP
Control Voltage input
Control Voltage Power Supply connections
G1-2
COIL_SUP_RTN
Control Voltage return
Control Option Jumpers – Points 1 to 16
G1-35,
G1-36
VCA
R/L Control Voltage for
O/P 1-16 (fused)
G1-37
JMP1
O/P Relays 1-8 mode
jumper point
Jumper to Pin G1-35 (VCA) for
Raise/Lower
Jumper to Pin G1-39 (MTA) for T/C
operation
G1-38
JMP2
O/P Relays 9-16 mode
jumper point
Jumper to Pin G1-36 (VCA) for
Raise/Lower
Jumper to Pin G1-40 (MTA) for T/C
operation
G1-39,
G1-40
MTA
Trip Bus For Channels
1 to 16
Control Option Jumpers – Points 17 to 32
G2-1,
G2-2
VCB
R/L Control Voltage for
O/P 17 to 32 (fused)
G2-3
JMP3
O/P Relays 17-24 mode
jumper point
Jumper to Pin G2-1 (VCB) for Raise/Lower
Jumper to Pin G2-5 (MTB) for T/C
operation
G2-4
JMP4
O/P Relays 25-32 mode
jumper point
Jumper to Pin G2-2 (VCB) for Raise/Lower
Jumper to Pin G2-6 (MTB) for T/C
operation
G2-5,
G2-6
MTB
Trip Bus For Channels
17 to 32
Master Close Relay Monitoring Points
G2-7
MCA
Master Close Bus for
Channels 1 to 16
Do
not
connect to load or power supply.
Use only for monitoring.
G2-8
MCB
Master Close Bus for
Channels 17 to 32
Do
not
connect to load or power supply.
Use only for monitoring.