Chapter 1: System operation
Vigilant VS1 and VS2 Technical Reference Manual
51
Reports
Test
Control
Program
⇩
Test
Walk Test Silent
Walk Test Audible
Test Fire
⇩
Walk Test Sil/Aud
All Devices
Zone
⇩
Zone
Number 01
Zone 01
⇩
To end a walk test:
Note:
To see the activation and restoration of all walk test events,
the panel must be reset
prior
to ending the walk test. Once the reset
is complete, you can end the walk test and view a walk test report.
1. Press the Menu button.
2. Choose
Test.
3. Choose Walk Test Silent or Walk Test Audible.
4. Choose either All Devices or Zone.
5. If you chose Zone, enter the zone ID of the zone for which you
are going to end the walk test.
6. Choose End to turn off the walk test. All of the devices that were
activated in the test are restored at this time.
7. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Start
End