Chapter 1: System operation
50
Vigilant VS1 and VS2 Technical Reference Manual
• If auxiliary power is resettable, the auxiliary power is
interrupted while the zone is reset.
• Input zones programmed as waterflow with retard require 10 to
15 seconds of activation to initiate the test signals.
• Devices programmed as alarm verify and
not in test mode
go
directly into alarm if activated (the alarm verification process is
bypassed).
• Once a device is tested, restore the device. For example, if you
are testing a pull station, reset the pull station before testing the
next device.
The panel terminates walk test if any of the following occur:
• There are 30 minutes of inactivity for the zone or device being
tested.
• Walk test is stopped by the user.
Reports
Test
Control
Program
⇩
Test
Walk Test Silent
Walk Test Audible
Test Fire
⇩
Enter Password
0000
⇩
Walk Test Sil/Aud
All Devices
Zone
⇩
Zone
Number 01
Zone 01
⇩
To start a walk test:
1. Press the Menu button.
2. Choose
Test.
3. Choose Walk Test Silent or Walk Test Audible.
4. Enter your password (the minimum of a level one password is
required).
5. Choose either All Devices or Zone.
6. If you chose Zone, enter the zone ID for the zone you are going
to conduct the walk test.
7. Choose
Start.
8. Conduct your walk test.
9. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.