Chapter 3: Programming
110
Vigilant VS1 and VS2 Technical Reference Manual
number (up to 20 digits).
Secondary receiver number: Enter the secondary receiver’s
phone number (up to 20 digits).
Format: CID
CID: Contact ID is the alarm format that the monitoring facility
(DACR) will receive. See "Contact ID event codes" for more
information.
Event notification: Set event notification (event reporting) to:
Device: Only device information is reported/transmitted, no
zone information. Note: This setting uses default device event
notification settings for reporting events. Refer to "Factory
default settings" for more information.
Zone: When a device is a member of a zone, only the zone
information is reported/transmitted, no device information.
Note: This setting uses default zone event notification settings
for reporting events. Refer to "Factory default settings" for
more information.
Event: Only the event type (alarm, supervisory, trouble, etc.) is
reported/transmitted, no device or zone information. Note:
This setting uses the default CMS event notification settings
for reporting events. Refer to "Factory default settings" for
more information.
Network
Account ID 676968
IP 000.000.000.000
Event Notif. Event>
⇩
Network
Receiver# 000
Line# 000
Save
NET options programming
Account ID
Enter the central monitoring station (CMS) account's six-digit ID
code.
IP
Enter the IP address for the CMS.
Event
notification
Set event notification (event reporting) to:
Device: Only device information is reported/transmitted, no
zone information. Note: This setting uses default device event
notification settings for reporting events. Refer to "Factory
default settings" for more information.
Zone: When a device is a member of a zone, only the zone
information is reported/transmitted, no device information.
Note: This setting uses default zone event notification settings
for reporting events. Refer to "Factory default settings" for
more information.
Event: Only the event type (alarm, supervisory, trouble, etc.) is
reported/transmitted, no device or zone information. Note:
This setting uses the default CMS event notification settings
for reporting events. Refer to "Factory default settings" for
more information.
Receiver
number
Enter the CMS receiver number. Specifies the CMS receiver
number that you want displayed in the message sent to the
receiver. This number is user-defined.
Line number
Enter the CMS receiver line number. Specifies the receiver's line
number that you want displayed in the message sent to the
receiver. This number is user-defined.