Chapter 3: Programming
152
Vigilant VS1 and VS2 Technical Reference Manual
Reports
Test
Control
Program
⇩
Program
Auto Program
Advanced Program
Date and Time
⇩
Enter Password
0000
⇩
Advanced Program
Panel Operation
Panel Events
Loop Events
⇩
Loop Events
Loop 1 Initializing
Loop 1 Fault
Loop 1 Map Fault
⇩
Loop 1 Initializing
Event Notification
⇩
Trouble
Printer Yes<>
Dialer Account 1&2
NET Yes<>
⇩
To program loop events:
1. Press the Menu button.
2. Choose
Program.
3. Choose Advanced Program.
4. Enter the level two password.
5. Choose Loop Events.
6. Select the loop event.
7. Choose
Event
Notification.
8. Set the event notification. See default settings in the table
above.
Printer: Yes or No. Specifies if event information is printed
Dialer:
Acct 1 & 2: Event information is sent to both dialer accounts
Acct 1: Event information is sent to dialer account one
Acct 2: Event information is sent to dialer account two
None: Event information is not sent to the dialer
NET: Yes or No. Specifies if event information is sent to the
connected network
CID: Contact ID event code (000 to 999)
9. When finished, choose Save.
10. Repeat steps 6 to 9 for each loop event.
11. Continue programming your system or press Menu to exit
menu mode.
Trouble
NET Yes
CID 110
Save