Appendix D: Applications
262
Vigilant VS1 and VS2 Technical Reference Manual
Follow Verification: Yes
Follow Pre Alarm: No
Note:
If alarm verification is required, set Device Type for Smoke
Verified, set Verification and Alt Verification as required, set
Follow Verification for No, and set Follow Pre Alarm for Yes.
3. Configure the CRR module as follows:
Device Type: Relay Silence
Message Line 1: SOUNDER_RLY_1
Message Line 2: As required
4. Configure the RM1 module as follows:
Device type: Monitor
Message Line 1: 24VDC_RISER
Message Line 2: SOUNDER_RLY_1
5. Configure
Correlation 01 as follows:
Inputs: All alarm signal-initiating devices
Outputs: All CRR modules used to active audible detector bases