Chapter 3: Programming
Vigilant VS1 and VS2 Technical Reference Manual
137
Event notification
Note:
Programming event notification here is only required if you selected "Event" as your
dialer account or network event notification setting. Refer to "Dialer programming" or "Network
programming" for more information.
Set the alarm, supervisory, monitor, trouble, disable, prealarm, alarm verify, maintenance alert,
and test event information by choosing one and then setting the notification information.
When finished, choose Save. See "Factory default settings" for CMS device event notification
default settings.
Dialer:
Acct 1 & 2: Event information is sent to both dialer accounts
Acct 1: Event information is sent to dialer account one
Acct 2: Event information is sent to dialer account two
None: Event information is not sent to the dialer
NET: Yes or No. Specifies if event information is sent to the connected network
CID: Contact ID event code (000 to 999)
Panel Configuration
Ann. Class
Annunciator
CMS Device
⇩
CMS Device
Dialer
Network
Swngr Shtdn Rp.200<>
⇩
To program CMS devices:
1. Access the panel configuration options menu. See "Panel
configuration options."
2. Choose CMS Device.
3. Choose the device you want to program.
4. Program each device and option using the "CMS device
programming" table above.
5. When you finish programming each device and option, choose
Save.
6. Continue programming your system or press Menu to exit
menu mode.
CMS Device
Swngr Shtdn Rp.200<>
Event Notification
Save