![GE Security Vigilant VS1 Technical Reference Manual Download Page 158](http://html.mh-extra.com/html/ge-security/vigilant-vs1/vigilant-vs1_technical-reference-manual_572057158.webp)
Chapter 3: Programming
148
Vigilant VS1 and VS2 Technical Reference Manual
Panel events programming
Panel events, such as reset, system startup, and battery low have
an event notification setting for contact ID, dialer, NET, and printer,
which controls where the event is sent when it takes place. Each
event has a factory default setting, which can be used with no
additional programming.
Factory default settings
Panel event
Printer
Dialer
NET
CID
Aux. power 1 (disable)
Yes
None
No
500
Aux. power 1 (trouble)
Yes
Acct 1
Yes
312
Aux. power 2 (disable)
Yes
None
No
500
Aux. power 2 (trouble)
Yes
Acct 1
Yes
312
Battery charger (disable) Yes
None
No
500
Battery charger (trouble)
Yes
Acct 1
Yes
309
Battery low (disable)
Yes
None
No
500
Battery low (trouble)
Yes
Acct 1
Yes
302
Battery missing (disable)
Yes
None
No
500
Battery missing (trouble)
Yes
Acct 1
Yes
311
Clear history
No
Acct 1
Yes
621
Common alarm
No
Acct 1
Yes
110
Common disable
No
Acct 1
Yes
500
Common monitor
No
None
No
140
Common supervisory
No
Acct 1
Yes
200
Common trouble
No
None
No
373
Common trouble for network dialer
No
None
Yes
373
Common trouble for telco dialer
No
Acct 1
No
373
Date No
Acct
1
Yes
625
Dialer disable/remote disconnect
Yes
Acct 1
Yes
551
Dialer line 1 fault (disable)
Yes
None
No
500
Dialer line 1 fault (trouble)
Yes
Acct 1
Yes
351
Dialer line 2 fault (disable)
Yes
None
No
500
Dialer line 2 fault (trouble)
Yes
Acct 1
Yes
352
Dialer deliver fail
Yes
Acct 1
Yes
354
Dialer normal test
No
Acct 1
No
602
Dialer abnormal test
No
Acct 1
Yes
608