Appendix B: Worksheets
Vigilant VS1 and VS2 Technical Reference Manual
223
Table 4: Longest allowable circuit path with 6 to 10 GSA-UMs or GSA-MABs configured for 2-wire smoke detectors
Maximum allowable wire distance using nontwisted, nonshielded and
twisted, nonshielded wire pairs (evenly distributed)
18 AWG
16 AWG
14 AWG
Detector
addresses
Module
addresses
ft. m ft. m ft. m
1 to 25
0
3543 1080 5629 1716 8952 2729
26 to 50
0
2818 859 4476 1364 7120 2170
51 to 75
0
2092 638 3323 1013 5285 1611
76 to 100
0
1365 416 2169 661 3450 1051
101 to 125
0
639 195 1015 309 1614 492
0 1
to
25
2895 882 4599 1402 7314 2229
1 to 25
1 to 25
2503 763 3976 1212 6324 1927
26 to 50
1 to 25
1778 542 2825 861 4493 1369
51 to 75
1 to 25
1053 321 1672 510 2660 811
76 to 100
1 to 25
327 100 519 158 825 252
101 to 125
1 to 25
0 0 0 0 0 0
0 26
to
50
1910 582 3035 925 4827 1471
1 to 25
26 to 50
1465 446 2327 709 3700 1128
26 to 50
26 to 50
740 225 1175 358 1869 570
51 to 75
26 to 50
14 4 23 7 36 11
76 to 100
26 to 50
0 0 0 0 0 0
101 to 125
26 to 50
0 0 0 0 0 0
0 51
to
75
1114 340 1770 539 2814 858
1 to 25
51 to 75
427 130 678 207 1079 329
26 to 50
51 to 75
0 0 0 0 0 0
51 to 75
51 to 75
0 0 0 0 0 0
76 to 100
51 to 75
0 0 0 0 0 0
101 to 125
51 to 75
0 0 0 0 0 0
0 76
to
100
114 35 182 55 289 88
1 to 25
76 to 100
0 0 0 0 0 0
26 to 50
76 to 100
0 0 0 0 0 0
51 to 75
76 to 100
0 0 0 0 0 0
76 to 100
76 to 100
0 0 0 0 0 0
101 to 125
76 to 100
0 0 0 0 0 0
0
101 to 125
0 0 0 0 0 0
1 to 25
101 to 125
0 0 0 0 0 0
26 to 50
101 to 125
0 0 0 0 0 0
51 to 75
101 to 125
0 0 0 0 0 0
76 to 100
101 to 125
0 0 0 0 0 0
101 to 125
101 to 125
0 0 0 0 0 0