Chapter 3: Programming
Vigilant VS1 and VS2 Technical Reference Manual
139
Event: Only the event type (alarm, supervisory, trouble, etc.) is
reported/transmitted, no device or zone information. Note: This setting uses the
CMS event notification settings for reporting events. Make sure your event
notification settings are correct. Refer to "CMS device programming" for more
information.
Line 1 and 2
Dialing:
Cut duration/supervision:
Program line 1 options, and then program line 2 options. When finished
programming each line, choose Save.
Select Tone or Pulse dialing.
Set the cut duration/supervision to Off or 10 to 120 seconds. Specifies the length of
time a phone line trouble is detected before reporting the trouble.
Tone wait seconds
Set tone wait to Off or 1 to 30 seconds. Specifies how long the dialer waits to get a
dial tone.
Call disconnect seconds
Set call disconnect to Off or 1 to 45 seconds. Specifies the length of time the dialer
seizes the line (to disconnect parallel devices) before attempting to dial out.
Test frequency days
Set test frequency to Off or 1 to 45 days. Specifies how often the dialer performs a
test call. Note: The "off" setting is not acceptable for UL/ULC installations. Refer to
"UL 864 programming requirements" for details.
Test time
Set the test time to the desired time of day for running the test.
Rings to answer
Set rings to answer to Off or 1 to 15 rings. Specifies how many rings before the dialer
answers incoming calls.
Ring type
Set ring type to Any or Normal. Specifies the type of ring expected when an
incoming call is received.
Callback
Select Enabled or Disabled.
Callback number
Enter the callback phone number (up to 20 digits). This specifies the phone number
that is used for call back.
Panel Configuration
Ann. Class
Annunciator
CMS Device
⇩
CMS Device
Dialer
Network
Swngr Shtdn Rp.200<>
⇩
Dialer
Type Single Line>
Account 1
Account 2
⇩
To program the dialer:
1. Access the panel configuration options menu. See "Panel
configuration options."
2. Choose CMS Device.
3. Choose
Dialer.
4. Program the dialer using the "Dialer programming options"
table above. For dialer default settings, see "Factory default
settings."
5. When you're finished programming each option, choose Save.
6. Continue programming your system or press Menu to exit
menu mode.
CMS Device
Swngr Shtdn Rp.200<>
Event Notification
Save