Chapter 3: Programming
Vigilant VS1 and VS2 Technical Reference Manual
163
2 wire verify Class A: Allows for the monitoring of two-wire conventional smoke detectors in a
Class A circuit (that require alarm verification)
Audible: Assigned to NACs connected to audible notification appliances that turn off when
Signal Silence is pressed
Visible: Assigned to NACs connected to visible notification appliance that do not turn off when
Signal Silence is pressed
Relay module
Relay nonsilence: For the connection of relay devices that do not follow signal silence.
Relay with silence: For the connection of relay devices that follow signal silence.
00:00:00 A001 D001
001 Trouble
Unconfigured Trouble
Ser# xxxxxxxxxx
⇩
Loop x Device xxx
Device type
⇩
Enter Password
0000
⇩
Add Loop x
Device 001
Device label
<-Continue <Back
⇩
Device 001
Zone 01<>
Label >
Correlation Groups
To add a device:
1. Install the device on your system.
The system recognizes the new device and displays a trouble
event, which indicates that there is an unprogrammed device.
2. Press
Enter.
The device details screen is displayed.
3. Press
Enter.
The Enter Password screen is displayed if you are not logged
on. If you are already logged on, the Add Device screen is
displayed; go to step 5.
4. Enter a level two password.
The Add Device screen is displayed.
5. Verify the device you are about to add, and then press Enter.
The Device programming menu is displayed. If the device is not
a valid device, "invalid device" is displayed and you won't be
able to program the device.
6. Program the device options using the "Device programming
options" table above.
⇩