Appendix B: Worksheets
210
Vigilant VS1 and VS2 Technical Reference Manual
Worksheet B: Auxiliary/smoke power current load
Devices
Qty
Standby
current (mA)
Alarm
current (mA)
Qty x Standby
current (mA)
Qty x Alarm
current (mA)
RPM
20
270
GSA-UM or -MAB [1]
2
17
RLCD(F)
98
113
RLCD-C(F)
99
115
RLED-C(F)
28
62
LED24
6
34
Totals (mA)
(transfer totals to Battery Calculation Worksheet)
Note
[1] Enter 1 regardless of how many are installed. Only the first GSA-UM or GSA-MAB in the alarm state draws
current. The other ones do not because the system load sheds additional modules in alarm.